• Accepts thermocouple, RTD, Ω, mV, Volt, or mA input (user selectable)
• Max temperature "Peak hold" display capture capability
• High set-point alarm LED warning with internal relay contact
• 24 VDC powered
• Analog retransmission output (to Data Logger)
Features:
• Full 4 Digit display with selectable decimal point position
• Single Channel
• Microprocessor based, 16 bit A/D
• °F/°C selectable or scalable in Engineering units
• Screw terminal connection
• Visible HI alarm LED + Relay output
• Process value Peak-Hold Capture function
• Analog retransmission output
Input Table (User Selectable)
Input Type Options |
Range Settings |
Thermocouple |
K, T, J, R, S, E |
RTD |
PT100, Cu50 |
Resistance |
0-375 ohms |
mV (DC) |
0-30 mV |
Volts (DC) |
0-5V, 1-5V, 0-10V |
mA (DC) |
0-10 mA, 0-20 mA, 4-20 mA |
Technical Specifications
Number of Inputs: |
1 |
Display Range: |
-1999 to +9999 |
LED Display: |
Red, 4-digit, 0.275 inch (7 mm high) |
LED Display Update Rate: |
0.5 second |
Microprocessor Sampling Rate: |
4 samples/second |
Microprocessor A/D Resolution: |
16 bit |
Accuracy: |
+/- 0.2% FS +/- 1 unit |
Environment: |
0 to 50C, 85% Max. RH (non-condensing) |
Operating Temperature: |
+32 to +125°F (0 to +50°C) |
Front Bezel Rating: |
IP51 |
Power: |
16 to 30 VDC (12 VDC powered available upon request) |
Current Draw: |
< 100 mA @ 24 VDC |
Analog Retransmission Output: |
0-20mA, 4-20mA (0-5VDC, 1-5VDC w/ included 250 ohm resistor) |
Alarm Relay Contact Rating: |
1A @ 30VDC |
Case Dimensions: |
1" x 2" x 3" (24mm x 48mm x 75mm) |
Panel Cutout Dimensions: |
1.77" x 0.87" (45 x 22 mm)(1/32 DIN) |
Weight: |
2.1 ounces |
We Ship World Wide! Europe, Asia, Australia, South America - Wherever you are, we will ship to you.